Products
EN-60598-1
EN-60598-2-22
EN-62034
Installation type:
· Wall surface.
Applications:
· Corridor, passageway, stairway, school, hotel, restaurant, commercial sites, retail, warehouse
1.- Manual test:
1) A short press (>1s) on the button initiates a function test lasting 5 seconds (battery capacity must be greater than 5% = charging 30 minutes).
2) Holding down the button (>10s) resets the timer (System Reset).
2.- Functional test:
The 5-second functional test, performed every 7 days, serves to check the functionality of the emergency unit, batteries and LED module. If a main power failure occurs while a bump test is being performed, the test will be postponed and the system will go into emergency operation.
3.- Autonomy Test (Automatic):
(2 hours): The test shall be performed exactly 16 hours after initial installation. The test shall be conducted every 180-182 days. 2 hour duration test in the first 180-182 days to verify battery capacity. 1.5 hour duration test is performed in the next 180-182 days and annually to verify the capacity of the batteries. A life test should only be initiated when the battery supply is fully charged. If a main supply failure occurs during a life test, the test will be postponed and the system will go into emergency operation. The indicator will flash green within 5 days if the endurance test was successful.
4.- Display of the test results: The system status is displayed locally by means of a two-colour LED indicator:
- Permanent green: Standby, System OK.
- Fast flashing green (0.25s on - 0.25s off): Functional test in progress.
- Slow flashing green (1s on - 1s off): Duration test in progress.
- Steady red: Lamp failure.
- Fast flashing red (0.25s on - 0.25s off): Battery capacity failure.
- Slow flashing red (1s on - 1s off): Battery failure.
- Green and red off: Battery operation.
Fault status: If an error is detected, the indicator LED will change to red. If the error has been corrected, reconnect the battery after switching off the main power.
Battery life test failure: After a battery change, press and hold the button (>10s) to reset the timer.

| H | A | B |
|---|---|---|
| 2,5 m | 1,7 m | 5,9 m |
| 3 m | 0,4 m | 5,4 m |
| 3,5 m | - | 2,7 m |
| 4 m | - | - |
| 4,5 m | - | - |
Spacing data calculated with no reflections and a maintenance factor of 0.9.
Compliant with the updated standard EN-1838:2024.
Minimum illuminance of 1 lux over a 1 m wide evacuation path.
The calculation of spacing distances is carried out considering the height of the light emission point, without taking into account the dimensions of the luminaire.
Product weight: 1.38 kg
Boxed product weight: 1.79 kg
Weight of box of 6 units: 11.59 kg
No hay información BC3 disponible
| Battery system | Control system | Emergency | Mains | Type* | Duration | Battery | Colour | Warranty | Certifications | Part number |
|---|---|---|---|---|---|---|---|---|---|---|
| Self-contained | 300 lm | 940 lm | M/NM | 1 h | 3.2V-1.5Ah LiFePO₄ | Black | 5 Years | CE CMIM | LOE3300LXP |