WALYA
SPECIFICATION
- Polycarbonate body
- Optics: Circular Lens + Hall Lens
- IP42
- IK04
- 150 lm – 300 lm
- Duration: 1 – 3 h · Battery: LFP
- Charging time: 12 h
- Supply: 230 V – 50 Hz
- LED temperature: 4000 ºK
- Working temperature: 0 ºC to +40 ºC AutoTest
- Wireless addressable monitoring
- DALI
- Warranty 5 year AutoTest & WSS Lithium
Downloads:
AENOR certificationENEC certificationCB Scheme certification
Available with:LiFePO4 Technology
Technical information
AutoTest
Emergency | Mains | Type* | Dur. | Battery | Ref. |
300 lm | - | NM | 1 h | 3.2V 1.5A/h LFP | LYW3300LX |
150 lm | - | NM | 3 h | 3.2V 1.5A/h LFP | LYW3150LX3 |
Wireless
Emergency | Mains | Type* | Dur. | Battery | Ref. |
300 lm | - | NM | 1 h | 3.2V 1.5A/h LFP | LYW3300LDW |
300 lm | 180 lm | M/NM | 1 h | 3.2V 1.5A/h LFP | LYW3300LDPW |
150 lm | - | NM | 3 h | 3.2V 1.5A/h LFP | LYW3150LD3W |
DALI
Emergency | Mains | Type* | Dur. | Battery | Ref. |
300 lm | 180 lm | M/NM | 1 h | 3.2V 1.5A/h LFP | LYW3300LAP |
150 lm | 90 lm | M/NM | 3 h | 3.2V 1.5A/h LFP | LYW3150LAP3 |
*NM: Non Maintained. The luminaire operates from emergency supply only upon failure of the normal mains supply.
*M/NM: Maintained/Non Maintained. With a switch which allows to select Maintained or Non Maintained mode function.
For black version, include “N” at the end of the reference. Luminous flux decreases by 18% in black colour version.
More information about our systems: AutoTest y Wireless
Here you can download the technical sheets and photometric curves corresponding to each reference:
Wireless
Ref. | Tech Sheet | Photometry |
LYW3300LDW | Tech Sheet | LDT |
LYW3300LDPW | Tech Sheet | LDT |
LYW3150LD3W | Tech Sheet | LDT |
Walya

- EN-60598-2-22
- AutoTest: EN-62034
- Wireless: ETSI EN 300 220
- DALI: EN 62386